EQUIPMENT: FIXED GAS SAMPLING

Function tested systemand found flow faultarising from allchannels.
SERVICE
REPORT
ISO 9001:2008 ACCREDITED
JOB NO : 20110431
sales@raycontrol.com
Page 1 of 5
VESSEL:
PORT:SG ANCHORAGE
DATE:04/05/2011
MAKE: HANLA
MODEL: HGS-100
DEFECTS/REASON FOR CALL: TROUBLESHOOT, CALLIBRATE AND SUPPLY
#
DESCRIPTION
REMARKS
FUNCTION TEST :-
Function tested system
and found flow fault
arising from all
channels.
1
Found 01 pump(for the
pump room) faulty.
HC detector for the
pump room was wrongly
adjusted.
TROUBLESHOOTING:-
HC detector for the
pump room was wrongly
adjusted.
2
There was low suction
around the filter
Flow fault arising with
the rise of flow meter.
_____________________________________________________________________________________
since 1981 and over 8000 jobs track records
TROUBLESHOOTING:-The pump room HC3detector setting wasrecalibrated to makerspecification
SERVICE
raycOntrol pte ltd
REPORT
7 TOH GUAN ROAD EAST #05-07 SINGAPORE
ISO 9001:2008 ACCREDITED
608599Tel:65630544 Fax:65600941
JOB NO : 20110431
sales@raycontrol.com
Company Reg No : 198602637N
Page 2 of 5
TROUBLESHOOTING:-
The pump room HC
3
detector setting was
recalibrated to maker
specifications.
_____________________________________________________________________________________
since 1981 and over 8000 jobs track records
TROUBLESHOOTING:-The filter wasserviced4andtested good suctionto the satisfaction ofthe vessel engineer.
SERVICE
raycOntrol pte ltd
REPORT
7 TOH GUAN ROAD EAST #05-07 SINGAPORE
ISO 9001:2008 ACCREDITED
608599Tel:65630544 Fax:65600941
JOB NO : 20110431
sales@raycontrol.com
Company Reg No : 198602637N
Page 3 of 5
TROUBLESHOOTING:-
The filter wasserviced
4
andtested good suction
to the satisfaction of
the vessel engineer.
SWAP faulty pump
and supply calibration
gas and conduct
FULL SYSTEM
CALIBRATION:-
The calibration for
5
both the ballast water
tanks and the pump room
was carried out to the
satisfaction of the
vessel engineer.
Calibration certificate
was issued to the
master.
_____________________________________________________________________________________
since 1981 and over 8000 jobs track records
FULL SYSTEMCALIBRATION
SERVICE
raycOntrol pte ltd
REPORT
7 TOH GUAN ROAD EAST #05-07 SINGAPORE
ISO 9001:2008 ACCREDITED
608599Tel:65630544 Fax:65600941
JOB NO : 20110431
sales@raycontrol.com
Company Reg No : 198602637N
Page 4 of 5
TESTING:-
Testing was carried out
by the vessel staff for
the ballast and pump
room system for HC, O2
and H2S gas for pre
6
alarm and alarm.
Pre alarm and alarm
arose for all the 3
systems to the
satisfaction of the
vessel engineer
SUPPLY:-
For calibration of the
system as per the
superindentent request
7
supplied 03 Nos of span
calibration bottles.
1. HC-01 Nos
2.
02-01 Nos
3. H2s-01 Nos
_____________________________________________________________________________________
since 1981 and over 8000 jobs track records
RECOMMENDATIONS:-1. Renew or replace the faulty pump.82. Calibrate the system annually.
SERVICE
raycOntrol pte ltd
REPORT
7 TOH GUAN ROAD EAST #05-07 SINGAPORE
ISO 9001:2008 ACCREDITED
608599Tel:65630544 Fax:65600941
JOB NO : 20110431
sales@raycontrol.com
Company Reg No : 198602637N
Page 5 of 5
RECOMMENDATIONS:-
1. Renew or replace the faulty pump.
8
2. Calibrate the system annually.
3. Do not let unauthorized personnel fiddle with the settings as the sensors
and detectors are very sensitive.
Report by: - G.GOPKUMAR (Service engineer.)