VESSEL: OVER FILL ALARM LIDEC L91 |
PORT: SINGAPORE |
JOBNO :20140507 |
|
EQUIPMENT: OVER FILL ALARM |
DATE:14/05/2014 |
||
MAKE: HANLA | HONEYWELL |
MODEL: LIDEC-L91 |
||
Lidec liquid level switches are liquid level sensors for overfill protection that ensure safety, simple, cost-effective maintenance. Lidec is a no-moving-parts liquid level detector. Application for High level alarms for tankers: Water ingress or Service tanks of all type of ship. |
|||
ITEM |
DESCRIPTION / REMARKS : |
||
1 |
JOB DESCRIPTION /DEFECT REPORTED :
Tank overfill alarm is erratic & highly sensitive. Alarm not getting reset after even reset alarm in CCR.
Checked the system initially found alarms were activated in #2(P) & #4(P) tanks even the tanks were empty.
|
||
2 |
CHECKING OF SAFETY BARRIER :
Checked and tested safety barrier found all ok.
|
||
3 |
TROUBLESHOOTING/SERVICE:
Checked local side PCB and sensors.
Found #2P tanks PCB card not working. Stimulated with good working PCB found the #2P tank overfill alarm working in order. Recommended to renew PCB.
#4P tank PCB setting found Wrong setting. Setting done, test and found working.
|
||
4 |
ADDITIONAL REQUESTED BY C/O CHECKING OF ALL TANKS
C/O and E/O requested to check all the 17 No’s of tank overfill alarm. As per C/O request we checked and stimulated the system , the results are,
#1(P) - Existing working in order #1(S) - Existing working in order #1(C) - Found PCB setting Wrong, setting done as per manul and working in order. #2(P) - Found PCB not working, PCB to be renew. #2(S) &(C) - Found PCB setting Wrong, setting done as per manul and working in order #3(P) &(C) - Existing working in order #3(S) - PCB found more sensitive couldn’t be stable. Recommended to renew PCB. #4(P) - Found PCB setting Wrong, setting done as per manul and working in order. #4(C) - Existing working in order #4(S) - Found both PCB and sensor element problem, recommended to Renew. #5(P) Found PCB not working, PCB to be renew. #5(S) - Found both PCB and sensor element problem, recommended to Renew. #5(C) - Existing working in order Slop (P)- Found PCB not working, PCB to be renew. Slop(S) - Existing working in order. |
||
5 |
RECOMMENDATION:
Recommended to renew the faulty PCB and Sensor element.
PCB card need to renew for the below Tanks:
#2(P), 3(S), 4(S), 5(P)&(S) and Slop (P)
Sensor element need to Renew for below Tanks: #4(S) & 5(S)
|
||
Copyright © 2016 raycOntrol pte ltd. All rights reserved. All brands and product names are trademark of their respective owners. raycOntrol pte ltd assumes no responsibility or liability for any misinterpretation, loss or damage incurred as a result of any use of the information and material contained within or downloaded from this website. All parties concerned are encouraged to conduct their own information verification or confirmation.
|
|||